Series 765 Pressure Vacuum Breakers are designed to be installed to provide protection against back siphonage of toxic or non-toxic liquids. They feature a durable bronze body and a check valve and air opening port in one assembly. Maximum Working Pressure: 150psi (10.3 bar).
Installation Instructions
1. Consult local codes for specific requirements and restrictions applicable
to your area. It is recommended that system supply pressure be at least
20psi (138 kPa).
2. These instructions apply to the FEBCO Series 765 PVB sizes
1⁄2" – 2"
(15 - 50mm) only. The valves may be installed only in the
orientation/flow direction as shown.
3. The Series 765 must be installed where it is accessible for periodic testing
and maintenance. Clearances shown in the installation views apply
to the exterior and interior installations and are only recommendations.
These minimums do not apply to removable protective enclosures.
Refer to local codes for actual requirements in your area.
4.
PRIOR TO INSTALLING THE VALVE INTO THE LINE, FLUSH THE
SUPPLY LINE OF ALL FOREIGN MATERIAL.
Failure to flush the supply
line may cause the check valves to become fouled and require disassembly
and cleaning. The device should be installed where some
spillage is not objectionable, as instantaneous siphon conditions and
pressure surges may cause “spitting”
5. When threading the device inline, place the wrench only on the ball
valve hex ends. Keep pipe dope (sealant) off the interior surfaces of the
valve. After installation fill the assembly with water. Test the valve
assembly to ensure correct operation.
Open the inlet ball valve to pressurize the device. Slowly open the outlet
ball valve to fill the downstream line.
NOTE:
The downstream pressure must be maintained above 5psi (34
kPa) to keep the spring loaded air inlet poppet closed.
NOTE:
All assemblies are tested at the factory for proper operation and
leakage. If the valve does not pass the field test, it is most likely due to
a fouled check valve. This is not covered by the factory warranty. The
valve cover(s) must be removed and the check seats inspected and
cleaned. Any damage or improper operation caused by pipeline debris or
improper installation / start-up is not included in the factory warranty.
In case of a possible warranty claim, contact your local supplier or
FEBCO Representative.
DO NOT REMOVE THE VALVE ASSEMBLY
FROM THE PIPELINE.
6. The assembly must be protected from freezing and excessive pressure
increases. Pressure increases can be caused by thermal expansion or
water hammer. These excessive pressure situations must be eliminated
to protect the valve and system from possible damage.
7. Plastic testcock plugs and tethers are provided (loose in box) for areas
that require them. Refer to FEBCO literature on PVB freeze protection,
“Freeze Protection 765.”